testo 6457 – flow transmitter 8 … 27 450 m³/h
Flow measurement - 8 ... 27 450 m³/h
- Suitable for large pipe diameters DN 65 - 250
- Direct compressed air measurement with simultaneous display of three measured values thanks to standard TFT display
- The sensor can be removed under pressure
The testo 6457 flow transmitter is used for measuring, monitoring and logging compressed air consumption and is therefore the ideal measuring instrument for detecting leaks in compressed air systems, allocating costs based on consumption and performing peak load management.
The testo 6457 measures the standard air flow in the compressed air according to the calorimetric principle, which means that the measurement method is independent of the process pressure and does not cause any permanent pressure loss.
The testo 6457 flow transmitter has a patented quick coupling, which allows the sensor to be removed under pressure. This is a great advantage, especially in the case of larger nominal widths, as these often involve main lines that do not allow pressure relief for maintenance purposes.
Flexible: Suitable for large pipe diameters DN 65 – 250
Clear overview: Direct compressed air measurement with simultaneous display of three measured values thanks to the standard TFT display.
Quick release: the sensor can be removed under pressure
Three measurement parameters in one instrument: flow rate, totalizer and temperature.
See the data sheet under the Download tab for full technical data.
Included in delivery
testo 6457 flow transmitter
Airflow measurement/adjustment range | See the datasheet under the PDF tab above for full technical data. |
Measurement range | DN 65 (2 ½“): 130 ... 31 280 l/min; 0,6 ... 143 m/s;8 ... 1 877 m³/h DN 80 (3“):183 ... 43 920 l/min; 0,6 ... 143 m/s;11 ... 2 635 m³/h DN 100 (4“): 315 ... 75 550 l/min; 0,6 ... 143 m/s; 19 ... 4 533 m³/h DN 125 (5“): 481 ... 115 400 l/min; 0,6 ... 143 m/s; 29 ... 6 923 m³/h DN 150 (6“): 708 ... 169 800 l/min;0,6 ... 143 m/s;43 ... 10 190 m³/h DN 200 (8“): 1 206 ... 289 200 l/min;0,6 ... 143 m/s;73 ... 17 350 m³/h DN 250 (10“): 1 908 ... 457 600 l/min;0,6 ... 143 m/s;115 ... 27 450 m³/h |
Temperature coefficient | “±0.07% of measured value |
Accuracy (measuring range) | Class 151: ±(3.1% of mv. + 0.5% of final value); Class 344: ±(6% of mv. + 0.6% of final value); air quality acc. ISO 8573-1:2010; at average temperature 23 °C |
Repeat accuracy | ±1.5% of measured value |
Max display | 0 ... 120% final |
Resolution | 0,9 l/min 0,1 m/s 0,05 m³/h |
Low Flow Shutdown LFC | Can be set by user. Factory setting 0.13% of final v. |
Measurement/adjustment area for totalizer | |
Measurement range | 0 ... 100 000 000 m³ | 0 ... 353 146 667,2 scf |
Max display | 0 ... 100 000 000 m³ | 0 ... 353 146 667,2 scf |
Temperature measurement/adjustment range | |
Measurement range | -10 ... 60 °C/14 ... 140 °F |
Max display | -24 ... 74 °C/-11,2 ... 165,2 °F |
Resolution | 0,2 °C / 0,5 °F |
Scope of use | |
Media | Compressed air |
Average temperature | -10 ... 60 °C/14 ... 140 °F |
Pressure load | max. 16 bar (> DN200 14 bar) |
Electrical data | |
Operating voltage | 18 ... 30 VDC (according to EN 50178 SELV/PELV) |
Power consumption | < 80 mA |
Protection class | III |
Protected against polarity reversal | Yes |
Outputs testo 6457 | |
Output signal | 1 analog; 1 pulse |
Number of outputs | 2 |
Analog output current | 4 ... 20 mA (scalable) |
Max. current load | < 150mA |
Pulse voltage | VDC - 2V |
Pulse duration | 0.002 ... 2 s (depending on pulse value) |
Max. load | 500 Ω |
Short circuit protection | Yes |
Temperature measurement | |
Accuracy | ± 0.5 K; (for media flow within the limits of the measurement range) |
Reaction time | |
Response time | 0,1 s; (dAP = 0) |
Temperature measurement | |
Response dynamics | t09 = 0,5 s |
Environmental conditions | |
Ambient temperature | 0 ... +60 °C |
Storage temperature | -20 ... +85 °C |
Moisture | Max. permissible relative humidity < 90% |
Protection class | IP 65; IP 67 |
Approvals / tests | |
EMF | DIN EN 60947-5-9 |
Vibration resistance | DIN EN 68000-2-6 | 5 g (10 ... 2 000 Hz) |
Mechanical data | |
Material in instrument housing | PBT-GF 20, PC (APEC), PBT-PC-GF 30; PPS GF 40; FKM |
Contact with the media | Materials: stainless steel or zinc-coated steel, FKM, PPS GF40, Al203 (ceramic), acrylate, glass-coated ceramic |
The length of the measuring tube | DN 65: 124 mm DN 80: 160 mm DN 100: 160 mm DN 125: 172 mm DN 150: 180 mm DN 200: 180 mm DN 250: 196 mm |
Pipe diameter | DN 65 (2 1/2") DN 80 (3“) DN 100 (4“) DN 125 (5“) DN 150 (6“) DN 200 (8“) DN 250 (10“) |
Weight testo 6456 (steel) | DN 65: 9,2 kg DN 80: 11,3 kg DN 100: 13,5 kg DN 125: 21,3 kg DN 150: 26,9 kg DN 200: 37,3 kg DN 250: 55,8 kg |
Weight testo 6457 (stainless steel) | DN 65: 11,1 kg DN 80: 13,2 kg DN 100: 15,4 kg DN 125: 23,2 kg DN 150: 28,8 kg DN 200: 39,2 kg DN 250: 57,7 kg |
Display / buttons | |
Display | Color screen - 1.44'' | pixel resolution - 128 x 128 |
Comments | m.v. = measured value endv. = full scale value Measurement, display and adjustment ranges refer to standard volume flow according to DIN ISO 2533. See the user manual for information on installation and operation. |
-
cabling
695:- Art.nr 0699 33935 meter long connection cable with screw thread M12 and loose ends. -
Power supplies for Hygrotest
2 590:- Art.nr 0554 1748Power supply 220 V - 24 V DC, for Hygrotest. Input: 110 ... 240 VDC. Output: 24 VDC/350 mA. -
Power supply unit (DIN rail mounting)
3 150:- Art.nr 0554 1749Mesh thread for DIN rail. Input: 85 ... 264 VAC | 110 ... 300 VDC. Output: 24 VDC/2.5 A.